LEONARD® ECO-MIX™ TA-300-LF Emergency Mixing Valve With Internal Cold Water By-Pass, Activates at Temperature 85 deg F, 1/2 in Inlet, Bronze

LEOTA300 MFG #: TA 300
  • Activates At Temperature: 85 deg F
  • Country of Origin: US
  • Finish: Rough Bronze
  • Inlet Size: 1/2 in
  • Manufacturer Name: Leonard Valve Company
  • Features and More

Features

  • DURA-trol® solid bi-metal thermostatic control
  • Locked temperature regulator set for 85 deg F
  • High temperature limit stop set for 90 deg F
  • Internal cold water bypass on failure of hot water supply standard on all models
  • Provide tepid water to eyewash or eye/face wash unit
  • Performance: On failure of hot water supply, internal cold water by-pass delivers cold water to the emergency fixture, minimum of 4 gpm at 30 psi, on failure of cold water supply, hot water is shut down
  • Has an integral wall mounting bracket
  • Certified to meet low lead C US requirements of wetted surface area containing less than 0.25% lead by weight
  • 180 deg F maximum supply temperature
  • 125 psi maximum supply pressure
  • 1/2 in outlet
  • 2 to 9 gpm flow rate
  • Dimension: 7 in W x 5 in D x 7 in H

Application

  • For Single Eyewash or Eye/Face Wash Units

Standards/Approvals/Certifications

  • ANSI/ISEA Z358.1-2014
  • ASSE 1071
  • CSA Certified